CS6 Fire Rating Ceiling 2 Hours

CS6 - Fire Rating Ceiling 2 Hours

Introduction

This ceiling system developed to meet the requirements of Fire Resistant up to  2 hours (FRL-120/120).

Suitable to applied at:

  • Laboratory.
  • Ceiling for Generator room.
  • Any other area that require Fire Resistance performance.

Supporting Material:

  • Frame: JayaBMS Hanger System (Bracket PN 220/221, Clip Adjuster PN 224, Rod PN 226), JayaBMS Top Cross Rail PN 202, JayaBMS Furring PN-205
  • Board: 4 Layer of Firestop 16mm
  • Jointing: JayaCompound as Jayaboard Recommendation.

Use Hitung Material fiture to help you figure total materials needed.

Specifications:

  • Fire Rating: (FRL -/120/120).
  • Weight: 54 Kg/m2

Notes:

  • All the materials above calculated based on a room with a size of (10x10m). Another room sizes should be considered further.
  • Suspension gap max. of 800mm
  • Primary frames gap max. of 900mm
  • Secondary frames gap max. of 400mm
  • All the materials above needs to be reconfirmed by the Contractor / Applicators regarding bookings material inquiry order.
  • Exclude waste material.

 

 

Information provided are for reference purpose only and due care has been taken to ensure accuracy at time of publication. Products, specifications and requirements may vary according to geographical locations and applications. As each project is unique, please contact your local Jayaboard representative for further assessment.